Demilitarization Plan Operation of the Chemical Agent Munitions Disposal System (CAMDS) at Tooele Army Depot. Inclosure Number 15. Dunnage Incinerator Testing
Author | : Robert L. Hanson |
Publisher | : |
Total Pages | : 54 |
Release | : 1977 |
ISBN-10 | : OCLC:227522281 |
ISBN-13 | : |
Rating | : 4/5 ( Downloads) |
Download or read book Demilitarization Plan Operation of the Chemical Agent Munitions Disposal System (CAMDS) at Tooele Army Depot. Inclosure Number 15. Dunnage Incinerator Testing written by Robert L. Hanson and published by . This book was released on 1977 with total page 54 pages. Available in PDF, EPUB and Kindle. Book excerpt: An air pollution engineering source sampling survey was conducted at Tooele Army Depot to evaluate particulate and visible emissions from the Transportable Disposal System (TDS) dunnage incinerator with respect to standards of 0.2 gr/scf and No. 1 Ringlemann. The waste charging rate was 500 lb/hr. The measured particulate emissions for the two required test runs were 0.113 and 0.190 gr/scf. The observed visible emission was essentially zero on the Ringlemann Scale. (Author).